| MODEL PRO810 (RS/RL) | |
| Volt-Amp | 10000 VA |
| Watt | 9000 W |
| Phase | Single Phase In / Single Phase Out |
| INPUT | |
| Low Line Transfer | 176 VAC ±3% @ 100% Load or 110 VAC ±3% @ 50% Load |
| Low Line Comeback | 186 VAC ±3% @ 100% Load or 120 VAC ±3% @ 50% Load |
| High Line Transfer | 300VAC ±3% |
| High Line Comeback | 290VAC ±3% |
| Frequency Range | 46~54Hz or 56Hz~64Hz |
| Power Factor Correction | = 0.99 @ 100% Load |
| OUTPUT | |
| Output Voltage | 208/220/230/240VAC |
| AC Voltage Regulation (Battery Mode) | ±1% |
| Frequency Range | 46~54Hz or 56~64Hz |
| Current Crest Ratio | 3:1 |
| Harmonic Distortion | = 2% THD, = 6% THD |
| Transfer Time | Zero |
| Waveform (Battery Mode) | Pure Sinewave |
| EFFICIENCY | |
| AC Mode | 90% |
| Battery Mode | 88% |
| Battery Type | 12V9AH |
| Battery No. | 20 |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Charging Current (max.) | 1A |
| Charging Voltage | 273VDC ±1% |
| INDICATOR | |
| LCD Panel | UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, Fault Conditions |
| Battery Model | Sounding every 4 seconds |
| Low Battery | Sounding every seconds |
| Overload | Sounding twice every seconds |
| Fault | Continuously sounding |
| GENERAL | |
| Dimension (mm) D×W×H | UPS Unit : 668×438×133 [3U] Battery Pack : 580×438×133 |
| Weight (kgs) | UPS Unit : 20 Battery Pack |
| Humidity | 20-90% Relative Humidity @ 0~40°C (Non-Condensing) |
| Noise Level | Less than 45dB @ 1 MeterLess than 55dB @ 1 Meter |
| Regulations | EN 62040-1:2008, EN 62040-2:2006, EN 61000-4-2:2009 |
| Smart RS232 | Support Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix and MAC |