PRO802ERS 2KVA/1800W Rack/Tower Master II Online UPS / AVR
Master II Series (1P/1P) 1K-3K provides better output power factor up to 0.9 with higher performance and efficiency for critical applications. It comes with programmable power management outlets which can extend available battery time to critical devices by shutting down unnecessary devices. It also comes with hot-swapping battery feature which helps to facilitate the replacement of the existing batteries without the hassle of having to shut the devices down. This UPS is suitable for laser printer and ultrasound system load.

Features:
  • True double-conversion
  • Output power factor 0.9
  • ECO and advanced ECO mode for energy saving
  • Output voltage regulation < 1%
  • Higher output crest radio 3:1
  • 50Hz/60Hz frequency converter mode
  • Programmable power management outlets
  • Emergency power off function (EPO)
  • Hot swappable battery design

  • GENERAL
    Model PRO802ERS
    Phase Single phase with ground
    Capacity 2000 VA / 1800 W
    INPUT
    Nominal Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
    Input Voltage Range 55-150 VAC or 110-300 VAC (Based on load at 50%)
    85-140VAC or 160-280VAC (Based on load at 100%)
    Frequency Range 40 Hz ~ 70 Hz
    Power Factor > 0.99 @ Nominall Voltage (100% load)
    THDI < 5% @ nominal input voltage
    OUTPUT
    Output Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
    Voltage Regulation ± 1 %
    Frequency Range (Synchronized Range) 47~ 53 Hz or 57 ~ 63 Hz
    Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
    Current Crest Ratio 3:1
    Harmonic Distortion < 2 % THD (Linear Load)
    < 4 % THD (Non-linear Load)
    AC Mode to Battery Mode Zero
    Inverter to Bypass 4 ms (Typical)
    Waveform (Batt. Mode) Pure Sinewave
    EFFICIENCY
    AC Mode 88%
    ECO Mode -
    Battery Mode 85%
    BATTERY
    Battery Type 12 V / 9 Ah
    Numbers 2
    Typical Recharge Time 4 hours recover to 90% capacity
    Charging Current (max.) 1.5 A
    Charging Voltage 27.4VDC ± 1%
    INDICATORS
    LCD UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
    ALARM
    Battery Mode Sounding every 5 seconds
    Low Battery Sounding every 2 second
    Overload Sounding every second
    Fault Continuously sounding
    PHYSICAL
    Dimension D x W x H (mm) 480×438×88
    Weight (Kgs) 20.6
    ENVIRONMENT
    Humidity 20-90 % RH @ 0- 40°C (Non-condensing)
    Noise Level Less than 50dBA @ 1 Meter
    MANAGEMENT
    Smart RS-232 / USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix and MAC
    Optional SNMP Power management from SNMP manager and web browser