GENERAL | |
Model | PRO802ERS |
Phase | Single phase with ground |
Capacity | 3000 VA / 2700 W |
INPUT | |
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Input Voltage Range | 55-150 VAC or 110-300 VAC (Based on load at 50%) 85-140VAC or 160-280VAC (Based on load at 100%) |
Frequency Range | 40 Hz ~ 70 Hz |
Power Factor | > 0.99 @ Nominall Voltage (100% load) |
THDI | < 5% @ nominal input voltage |
OUTPUT | |
Output Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Voltage Regulation | ± 1 % |
Frequency Range (Synchronized Range) | 47~ 53 Hz or 57 ~ 63 Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | < 2 % THD (Linear Load) < 8 % THD (Non-linear Load) |
AC Mode to Battery Mode | Zero |
Inverter to Bypass | 4 ms (Typical) |
Waveform (Batt. Mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | 90% |
ECO Mode | - |
Battery Mode | 88% |
BATTERY | |
Battery Type | 12 V / 9 Ah |
Numbers | 6 |
Typical Recharge Time | 4 hours recover to 90% capacity |
Charging Current (max.) | 1.5 A |
Charging Voltage | 82.1VDC ± 1% |
INDICATORS | |
LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every seconds |
Fault | Continuously sounding |
PHYSICAL | |
Dimension D x W x H (mm) | 600×438×88 |
Weight (Kgs) | 28 |
ENVIRONMENT | |
Humidity | 20-90 % RH @ 0- 40°C (Non-condensing) |
Noise Level | Less than 50dBA @ 1 Meter |
MANAGEMENT | |
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix and MAC |
Optional SNMP | Power management from SNMP manager and web browser |